{"product_id":"vmp-49-5","title":"Fulton VMP-49.5 VMP 49.5 BHP Steam Boiler","description":"\u003cp\u003eThe VMP (Vertical Multi-Port) is built for heavy-duty steam duty, with a pressure vessel 30% thicker than ASME requires and heavy-walled schedule 80 flue pipes.\u003c\/p\u003e\u003cp\u003eFulton lists fuel-to-steam efficiency up to 84%, steam quality above 99% and linkageless controls with turndown up to 8:1. The tubeless design has no tubes to replace and a compact vertical footprint.\u003c\/p\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003cth\u003eModel\u003c\/th\u003e\n\u003ctd\u003eVMP-49.5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSize\u003c\/th\u003e\n\u003ctd\u003e49.5 BHP\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eType\u003c\/th\u003e\n\u003ctd\u003eSteam boiler\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFuel input, natural gas (CFH)\u003c\/th\u003e\n\u003ctd\u003e1,974\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFuel input, propane (CFH)\u003c\/th\u003e\n\u003ctd\u003e790\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFuel input, #2 oil (CFH)\u003c\/th\u003e\n\u003ctd\u003e14.1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSteam output (lb\/hr)\u003c\/th\u003e\n\u003ctd\u003e1,708\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eOutput (MBH)\u003c\/th\u003e\n\u003ctd\u003e1,658\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eWater content, operating (gal)\u003c\/th\u003e\n\u003ctd\u003e231\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eHeight w\/o trim (in)\u003c\/th\u003e\n\u003ctd\u003e98\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eHeight w\/ trim (in)\u003c\/th\u003e\n\u003ctd\u003e109\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eWidth w\/o trim (in)\u003c\/th\u003e\n\u003ctd\u003e58\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eWidth w\/ trim (in)\u003c\/th\u003e\n\u003ctd\u003e87\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eDepth (in)\u003c\/th\u003e\n\u003ctd\u003e101\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eBurner pull (in)\u003c\/th\u003e\n\u003ctd\u003e115\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eSteam outlet, 150 psi trim (in)\u003c\/th\u003e\n\u003ctd\u003e3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFlue outlet (in)\u003c\/th\u003e\n\u003ctd\u003e12\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eShipping weight (lb)\u003c\/th\u003e\n\u003ctd\u003e6,160\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eOperating weight (lb)\u003c\/th\u003e\n\u003ctd\u003e8,085\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFuel options\u003c\/th\u003e\n\u003ctd\u003eNatural gas, dual fuel, propane, #2 fuel oil, bio-fuel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eApprovals shown by Fulton\u003c\/th\u003e\n\u003ctd\u003eASME, UL\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eEfficiency (per Fulton)\u003c\/th\u003e\n\u003ctd\u003eUp to 84%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth\u003eFulton lead time, as listed\u003c\/th\u003e\n\u003ctd\u003eVaries, consult factory\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003cp\u003e\u003cstrong\u003eWarranty:\u003c\/strong\u003e Warranty is administered directly by Fulton under its standard commercial terms.\u003c\/p\u003e","brand":"Fulton","offers":[{"title":"Default Title","offer_id":67666969395569,"sku":"VMP-49.5","price":110000.0,"currency_code":"CAD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0927\/1689\/2529\/files\/VMP_gray_1fe341d9-23d0-4959-8766-456fde8276d7.png?v=1791480208","url":"https:\/\/harrislaundryequipment.ca\/products\/vmp-49-5","provider":"Harris Laundry Equipment","version":"1.0","type":"link"}